Case of damage: cuffs from groundwater pipe
Metallography (longitudinal section)
Austenitic structure with dense accumulation of sulphide lines
Formation of local galvanic cells
Remedy:
Low sulphurized steel grade
Limitation of grain size and sulfide granularity when using 1.4305